Technical parameters | GRL8-01 | GRL8-02 |
Function | 2 level contorl mode | 2 or 1 level contorl mode |
Supply terminals | A1-A2 | |
Voltage range | AC/DC 24-240V(50-60Hz) | |
Input | max.2VA | |
Supply voltage tolerance | -15%;+10% | |
Sensitivity ( input resistance) | adjustable in range 5 kΩ -100 kΩ | |
Voltage in electrodes | max. AC 5 V | |
Current in probe | AC <0.1 mA | |
Time response | max. 400 ms | |
Max. capacity length | 800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ) | |
Max. capacity of probe cable | 400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ) | |
Time delay (t) | adjustable, 0.1 -10 s | |
Accuracy in setting (mechanical) | ± 10 % | |
Temperature coefficient | 0.05%/ºC,at=20ºC(0.05%ºF,at=68ºF) | |
Output | 1×SPDT | |
Current rating | 1×10A(AC1) | |
Switching voltage | 250VAC/24VDC | |
Min.breaking capacity DC | 500mW | |
Output indication | red LED | |
Mechanical life | 1×107 | |
Electrical life(AC1) | 1×105 | |
Reset time | max.200ms | |
Operating temperature | -20ºC to+55ºC(-4ºFto131ºF) | |
Storage temperature | -35ºC to+75ºC(-22ºFto158ºF) | |
Mounting/DIN rail | Din rail EN/IEC 60715 | |
Protection degree | IP40 for front panel/IP20 terminals | |
Operating position | any | |
Overvoltage cathegory | III. | |
Pollution degree | 2 | |
Max.cable size(mm 2) | solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12) | |
Tightening torque | 0.8Nm | |
Dimensions | 90×18×64mm | |
Weight | 70g | 72g |
Standards | EN 60255-1 |