··········This link price is only for GPS8-03 63A···········
Product Description
Applications
-Overvoltage,undervoltage and overcurrent protection for householdequipment.
Feature
-Voltage/current(True RMS)monitoring and protection.
-Use true RMS measurement.
-Double bus wiring design stronger ability.
-Over/under voltage value and over-current value can be set.
-Self reset after fault.
-Digital display voltage,current value,fault status can be displayed by LED.
-1-MODULE,DIN rail mounting.
Product Parameters
|
GPS8-03 |
Function |
Over voltage,under voltage and over current |
Rated supply voltage |
AC220V(L1,L2,L3-N) |
Rated supply frequency |
45~65Hz |
Operation voltage range |
80V~400V(L1,L2,L3-N) |
Rated operational current |
63A(AC1) |
Burden |
AC max.3VA |
Over voltage operation value |
OFF,230V~300V |
Under voltage operation value |
140V~210V,OFF |
Over/under voltage action delay |
0.1s~10s |
Over current operation value |
1A~63A |
Over current action delay |
2s~600s |
Voltage unbalance value |
20V~99V |
Voltage unbalance action time |
10s |
Power-up delay |
2~600s |
Reset time |
2~900s |
Measurement error |
≤1% |
Electrical life(AC1) |
1×104 |
Mechanical life |
1×106 |
Operating temperature |
-20ºC~+60ºC |
Storage temperature |
-35ºC~+75ºC |
Mounting DIN rail |
Din rail EN/IEC 60715 |
Protection degree |
IP40 for front panel/IP20 terminals |
Operating position |
any |
Overvoltage cathegory |
III |
Pollution degree |
2 |
Dimensions |
82×72×68mm |
Weight |
376g |
|
|
|
|