Customization: | Available |
---|---|
Theory: | Time Relay |
Usage: | Time Relay |
Still deciding? Get samples of US$ 5/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Applications:
Multifunction time relay can be used for electrical appliances, control of lights, heating, motors, pumps and fans (10 functions, 10 time ranges, multi-voltage).
Feature:
-10 functions:
8 time functions controlled by supply voltage
2 time functions controlled by control input
-Comfortable and well-arranged function and time-range setting by rotary switches.
-Time scale 0.1 s - 10 days divided into 10 ranges.
-Relay status is indicated by LED.
-1-MODULE,DIN rail mounting.
GRT8-N1 | GRT8-N2 | |
Function | A,As,Aw,B,Bs,Bw,Cs,Ds,Fe,Js | |
Supply terminals | A1-A2 | |
Voltage range | AC/DC 12-240V(50-60Hz) | |
Burden | AC 0.09-3VA/DC0.05-1.7W | |
Voltage range | AC 230V(50-60Hz) | |
Power input | ACmax.6VA/1.3W | AC max.6VA/1.9W |
Supply voltage tolerance | -15%;+10% | |
Supply indication | green LED | |
Time ranges | 0.1s-10days,ON,OFF | |
Time setting | potentionmeter | |
Time deviation | 10%-mechanical setting | |
Repeat accuracy | 0.2%-set value stability | |
Temperature coefficient | 0.05%/C,at=20ºCC(0.05%°,at=68°F) | |
Output | 1×SPDT | 2×SPDT |
Current rating | 1×16A(AC1) | 2×16A(AC1) |
Switching voltage | 250VAC/24VDC | |
Min.breaking capacity DC | 500mW | |
Output indication | red LED | |
Mechanical life | 1×10000000 | |
Electrical life(AC1) | 1×100000 | |
Reset time | max.200ms | |
Operating temperature | -20ºC to+55ºC(-4°F to 131°F) | |
Storage temperature | -35ºC to +75ºC(-22°Fto 158°F) | |
Mounting/DIN rail | Din rail EN/IEC 60715 | |
Protection degree | IP40 for front panel/IP20 terminals | |
Operating position | any | |
Overvoltage cathegory | III | |
Pollution degree | 2 | |
Max.cable size(mm²) | solid wire max.1×2.5or2×1.5/with sleeve max.1×2.5(AWG 12) | |
Dimensions | 90×18×64mm | |
Weight | 1×SPDT:W240-62g,A230-60g | |
2×SPDT:W240-82g,A230-81g | ||
Standards | EN 61812-1.IEC60947-5-1 |