GRT8-EC | |
Function | ON delay,Delay off |
Supply terminals | A1-A2(AC230V,AC380V),A1-A3(AC/DC24V) |
Voltage range | AC230V(50-60Hz)orAC/DC24V,AC380V(50-60Hz) |
Power input | AC max.6VA/1.3W |
Supply voltage tolerance | -15%;+10% |
Supply indication | green LED |
Time ranges | 0.1s-10day |
Time setting | potentiometer |
Time deviation | ≤10% |
Repeat accuracy | 0.2%-set value stability |
Temperature coefficient | 0.05%/ºC,at=20ºC(0.05%°F, at=68°F) |
output | 1×SPDT |
Current rating | 1×10A(AC1) |
Switching voltage | 250VAC/24VDC |
Min.breaking capacity DC | 500mw |
Output indication | red LED |
Mechanical life | 1×10^7 |
Electrical life(AC1) | 1×10^5 |
Resettime | max.200ms |
Operating temperature | -20ºC to+55ºC(-4°F to 131°F) |
Storage temperature | -35ºCto+75ºC (-22°F to 158°F) |
Mounting/DIN rail | Din rail EN/IEC 60715 |
Protection degree | IP40 for front panel/IP20 terminals |
Operating position | any |
overvoltage cathegory | 3 |
Pollution degree | 2 |
Max.cable size(mm²) | solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG12) |
Dimensions | 90×18×64mm |
Weight | 52g |
Standards | EN61812-1,IEC60947-5-1 |
Suppliers with verified business licenses