Product Description
Applications:
-It is used for delayed switching of lights in the corridors, entrances, stairways, and halls or for the delayed finish of fans (WC, bathroom, etc.).
Feature:
-10 functional modes
-It has a zero-crossing switching ability.
-Voltage range: AC 230 V, clamp terminals.
-Relay status is indicated by LED.
-1-MODULE, DIN rail mounting.
|
GRT8-LM |
Function |
delay off reacting to contact switching |
Supply terminals |
L-N |
Voltage range |
AC 230V(50-60Hz) |
Power input |
AC max.6VA/1.3W |
Supply voltage tolerance |
-15%;+10% |
Supply indication |
green LED |
Time ranges |
AUTO:0.5-20min ON OFF |
Time setting |
potentiometer |
Time deviation |
10%-mechanical setting |
Repeat accuracy |
0.2%-set value stability |
Minimum power time |
200ms |
Glow tubes connections |
Yes(N-3 or L-3) |
Max. amount of glow lamps |
230V,max.75pcs(Measured with glow lamp0.68mA/230VAC) |
Temperature coefficient |
0.05%/ºC,at=20ºC(0.05%°F,at=68°F) |
Output |
1×SPDT(zero-crossing switching) |
Current rating |
16A/AC1 |
Switching voltage |
250VAC/24VDC |
Min. breaking capacity DC |
500mW |
Output indication |
red LED |
Mechanical life |
1×10000000 |
Electrical life(AC1) |
1×100000 |
Reset time |
max.200ms |
Operating temperature |
-20ºCto+55ºC(-4°F to 131°F) |
Storage temperature |
-35ºCto+75ºC(-22F to 158°F) |
Mounting/DIN rail |
Din rail EN/IEC60715 |
Protection degree |
IP40 for front panel/IP20 terminals |
Operating position |
any |
Overvoltage cathegory |
III. |
Pollution degree |
2 |
Max.cable size(mm²) |
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12) |
Dimensions |
90×18×64mm |
Weight |
65g |
Standards |
EN61812-1,IEC60669-2-3,IEC60947-5-1 |
|
|
Certifications
Packaging & Shipping
Company Profile